Step 1 - Unscrew the screws of Positioner.
Step 2 - There will be four Hard Buttons
and one LCD Display.
Step 3 - The Hard buttons are for Mode, Up,
Down and Enter.
Step 4 – Press Up+Down+Enter Hard buttons
together. As soon as LCD will display P1.0 Unpress Enter. P1.0 should be set as
per Condition (Linear/Rotary). After setting Condition Unpress Up+Down. The LCD
will display 1…2…3…
Step 5 – Press Mode+Enter+Up Hard buttons
together. Continuously Press Up button. As soon as LCD will display P11.0 is
Inactive. Now, Unpress Mode+Enter.
Step 6 – Press Enter Button until LCD
Display 1…2…3… P11.0 is active that will be displayed in LCD.
Step 7 – Press Mode+Up P11.1 for FS Load Function and Enter the Hard
Button. The LCD will display Complete and will display 1…2…3...
Step 8 – Press Mode+Down P11.0 shows active
and then press Enter and make it Inactive and further LCD displays 1…2…3..
Step 9 –
Press Mode+Up and keep on pressing Up until P11.3 is not displayed when
it is displayed configure in NV save
.Press Enter that will LCD Display 1…2…3…(Position Sense)
Step 10 – Press Mode+Up until it will show
Manual in Display. Then Press Down Button continuously to change the present
value to 0. Then further press Up continuously to make present value 75(Valve
Open and Close Accordingly in Manual).
Step 11 – Press Enter+Up+Down will display
P1.0 and as soon as the LCD shows unpress Enter button.P1.0 is linear. LCD will
display 1….2…3….
Step 12 – Press Mode+Up LCD will display
P1.1, Press Enter LCD will display 1…2…3… the Positioner will automatically run
for Calibration. The LCD will display 10...20...40... …200 and LCD will Display
complete.
·
Step 10 – Manual Calibration
·
Step 12 – Auto Calibration.