The below figure gives a block diagram of power generation control. On receiving turbine governor demand signals
from the Automatic Boiler Control (ABC), the governor is put into operation,
and main steam flow changes. The flow
rate of main steam fed to the turbine is converted into generated energy by the
turbine generator.
Conventional governor
control has been obtained by driving it directly with the turbine according to
the control signals. These signals are
amplified by a proportional plus integral controller from the load dispatching
values and the deviation signal of generator energy. To further improve overall control in this case
the main steam flow control has been added.
Also the cascaded control method that incorporates the above main steam
flow control, has been included as a sub unit of generator energy control. Fig
4.1 gives a block diagram of power generation control. On receiving turbine governor demand signals
from the Automatic Boiler Control (ABC), the governor is put into operation,
and main steam flow changes. The flow
rate of main steam fed to the turbine is converted into generated energy by the
turbine generator.
Conventional governor
control has been obtained by driving it directly with the turbine according to
the control signals. These signals are
amplified by a proportional plus integral controller from the load dispatching
values and the deviation signal of generator energy. To further improve overall control in this case
the main steam flow control has been added.
Also the cascaded control method that incorporates the above main steam
flow control, has been included as a sub unit of generator energy control.
1.
Dispatching Value of Main
Steam Flow Rate
The
selection of main steam flow rate values in the turbine following mode is
different from that of the coordinated control mode.
a) Coordinated control mode (Not turbine
following mode)
The
dispatching values of the main steam flow rate are decided by adding advance
signals based on the load dispatching values to corrected values of generated
energy control.
b) Turbine following mode
Dispatching
values of the main steam flow rate are decided by correcting the program
setting point based on the total fuel flow rate of boiler input using the
deviation signals of the main steam pressure.
2. Upper and Lower Limits Using Main Steam
Pressure
Stable plant operation
cannot be achieved if there is wide variation of main steam pressure, which
exceeds the specified value. Pressure
should be immediately restored to its specified value.
Large variation in main
steam pressure when operating under coordinated control is caused by a response
delay of the boiler. In order to lessen
this variation, main steam pressure must be controlled by the turbine using a
turbine governor which provides the most rapid effect on the main steam
pressure.
3. Turbine Governor Control
Main steam flow rate
deviation signals are given to the proportional plus integral controller
through a deviation limiting circuit for main steam pressure. Governor opening signals, amplified by the
proportional plus integral controller, will send turbine governor control
signals after having passed through a manual/auto changing circuit.
No comments:
Post a Comment
Note: Only a member of this blog may post a comment.